OEM Wireless Sensors
|
| |
|
|
| |
| |
 |
|
Wireless Temperature Sensor
The wireless temperature sensor uses a thermistor to accurately measure temperatures from -20°C to 85°C. Perfect for slower changing temperatures and critical applications such as facilities or rooms. User customization allows you to set the frequency of readings and the ability to set thresholds for "Alarms", "Alerts" and "FYIs".
- Accurate to +/- 0.5°C (1.0°F).
- Temperature range of -20°C to 85°C.
- Custom leads are available for advanced sensor placement.
« Technical Specifications
| OEM Wireless Temperature Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Thermistor Specifications |
|
|
| Thermistor Operating Range |
-40°C to 125°C |
|
| Battery Operating Range |
-20°C to 85°C |
|
| Accuracy @ 25°C |
+/- 1% |
|
| Resistance @ 25°C |
10K ± 1% |
|
| B-Constant (25°C – 50°C) |
3380 ± 1% |
|
| Permissive Operating Current @ 25°C |
0.38 mA |
|
| Rated Electric Power @ 25°C |
15 mW |
|
| Dissipation Constant @ 25°C |
1.5mW/°C |
|
| Time Constant @ 25°C |
7 sec |
|
| RoHS |
Compliant |
|
|
|
| |
| |
 |
|
Wireless Water Sensor
The wireless water sensor alerts you of potential property damage that results from flooding or leaks. Place this sensor anywhere flooding or faulty plumbing could cause a problem. This sensor can also be used to detect a lack of water, allowing you to know when a container is nearing empty.
- Senses immediate pressence or non-pressence of water.
- Can be used for detection of any non-cumbustable liquid.
- Variety of lead lengths available.
« Technical Specifications
| OEM Wireless Water Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Water Sensor Specifications |
|
|
| Supply Voltage |
2.0 - 3.6 V |
|
| Current Consumption |
0.5 µA |
|
| Operating Temperature |
[-85°C to +150°C] |
|
| |
|
|
| Absolute Maximum Ratings: |
|
|
| Supply Voltage: |
[-0.3 to 3.9 V] |
|
| Storage Temperature: |
[-50°C to +150°C]* |
|
| *Core unprogrammed |
|
|
|
|
| |
| |
 |
|
Wireless Light Sensor
The wireless light sensor can be user calibrated for baselines of light and dark, and will detect the pressence or non-pressence of light according to those baselines. Using our monitoring software, alerts can be setup for when a light threshold has been met.
- Sense the pressence or non-pressence of light.
« Technical Specifications
| OEM Wireless Light Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Phototransistor Specifications |
|
|
| Collector Emitter Breakdown Voltage (0.1 mA) |
6 V |
|
| Collector Dark Current (5 VCE) |
3 nA typ. |
|
| Collector Emitter Capacitance (Vce=0, f=1MHz, E=0) |
16 pF |
|
| Collector Light Current (5 VCE, 20 lx) |
5 to 24µA |
|
| Collector Light Current (5 VCE,100 lx) |
75µA |
|
| Angle of Half Sensitivity |
±50 degrees |
|
| Wavelength of Peak Sensitivity |
570 nm |
|
| Range of Spectral Bandwidth |
440 to 800 nm |
|
| Collector Emitter Saturation Voltage (20 lx, 1.2 µA) |
0.1 V |
|
| RoHS |
Compliant |
|
| |
|
| Absolute Maximum Ratings (Ta = 25 C) |
|
| Collector Emitter Voltage |
6 V |
|
| Emitter Collector Voltage |
1.5 V |
|
| Collector Current |
20 mA |
|
| Power Dissipation |
100 mW (Tamb≤55°C) |
|
| Junction Temperature |
100 °C |
|
| Operating Temperature Range |
[-40°C to +85°C] |
|
| Storage Temperature Range |
[-40°C to +100°C] |
|
| Soldering Temperature |
260°C (t≤5 s, 2 mm distance to package |
|
| Thermal Resistance Junction/Ambient |
230 K/W (J-STD-051,soldered on PCB) |
|
|
|
| |
| |
 |
|
Wireless Open/Closed Sensor
The wireless open/closed sensor provides information on the status of doors, windows, cabinets, etc. Know if a building or area is being accessed when it should not be, or if a door or window has been left open.
- Sense immediate access.
- Sense if a door, window, drawer has been left open.
« Technical Specifications
| OEM Wireless Open Closed Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Movement Sensor Specifications |
|
|
| Supply Voltage |
0.5 to 12VDC |
|
| Current Sink |
0.00025 to 5 mA |
|
| Operating Temperature |
0°C to 70°C |
|
| Sensitivity |
0.05g – 0.10g OR 10g OR 35g OR 60g OR 150g |
|
| RoHS |
Compliant |
|
| |
|
| Magnetic Sensor Specifications |
|
|
| Power Supply Voltage |
-0.1 to 4.5 VDC |
|
| Output Current |
± 5 mA |
|
| Power Dissipation |
536 mW |
|
| Operate Point |
South: max 5 mT, North: - 5 mT |
| Release Point |
South: 0.6 mT, North: -0.6 mT |
|
| Period |
Max 100 mS |
|
| Supply Current |
8.0 µA typ, 12.0 µA max |
|
| Operating Temperature |
-40°C to 85°C |
|
| Storage Temperature |
-40° to +125°C |
|
| RoHS |
Compliant |
|
| (Vdd = 1.80 V, Ta = 25 C) |
|
|
| |
|
| Absolute Maximum Ratings (Ta = 25 C) |
|
|
| Power Supply Voltage |
[-0.1 - 4.5 V] |
|
| Output Current |
± 0.5 mA |
|
| Operating Temperature |
-40°C to 85°C |
|
| Storage Temperature |
-40° to +125°C |
|
|
|
| |
| |
 |
|
Wireless ID Sensor
The wireless ID sensor can be used as a digital ID tag for an object allowing you to track its contents and tell if it is on premises or not.
- Measure the presence of an object or asset.
- Assign contents to an object for tracking.
« Technical Specifications
| OEM Wireless ID Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Active RF ID Sensor Specifications |
|
| Supply Voltage |
2.0 - 3.6 V |
|
| Current Consumption |
0.7 µA (sleep mode) |
|
| Operating Temperature |
[-40°C to +85°C] |
|
| Storage Temperature: |
[-50°C to +150°C]* |
|
| |
|
| Absolute Maximum Ratings: |
|
| Supply Voltage: |
[-0.3 to 3.9 V] |
|
| *Core unprogrammed |
|
|
|
|
| |
| |
 |
|
Wireless Magnetic Pressence Sensor
The wireless magnetic presence sensor can be used to detect the presence of a magnetic source. Place a magnet strip on a motor or machinery to measure movement and placement.
- Measure and track RPMs.
- Sense presence and movement.
« Technical Specifications
| OEM Wireless Magnetic Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** Hardware can not withstand negative voltage. Take care when connecting a powered device.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Movement Sensor Specifications |
|
|
| Supply Voltage |
0.5 to 12VDC |
|
| Current Sink |
0.00025 to 5 mA |
|
| Operating Temperature |
0°C to 70°C |
|
| Sensitivity |
0.05g – 0.10g OR 10g OR 35g OR 60g OR 150g |
|
| RoHS |
Compliant |
|
| |
|
| Magnetic Sensor Specifications |
|
|
| Power Supply Voltage |
-0.1 to 4.5 VDC |
|
| Output Current |
± 5 mA |
|
| Power Dissipation |
536 mW |
|
| Operate Point |
South: max 5 mT, North: - 5 mT |
| Release Point |
South: 0.6 mT, North: -0.6 mT |
|
| Period |
Max 100 mS |
|
| Supply Current |
8.0 µA typ, 12.0 µA max |
|
| Operating Temperature |
-40°C to 85°C |
|
| Storage Temperature |
-40° to +125°C |
|
| RoHS |
Compliant |
|
| (Vdd = 1.80 V, Ta = 25 C) |
|
|
| |
|
| Absolute Maximum Ratings (Ta = 25 C) |
|
|
| Power Supply Voltage |
[-0.1 - 4.5 V] |
|
| Output Current |
± 0.5 mA |
|
| Operating Temperature |
-40°C to 85°C |
|
| Storage Temperature |
-40° to +125°C |
|
|
|
| |
| |
 |
|
Wireless Activity Sensor
The wireless activity sensor detects sudden movement or non-movement of a given device or surface, and alerts you of the change.
- Detect sudden movement.
- Tell if a motor or machine is on or off.
« Technical Specifications
| OEM Wireless Activity Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Activity Sensor Specifications |
|
|
| Supply Voltage |
0.5 to 12VDC |
|
| Current Sink |
0.00025 to 5 mA |
|
| Operating Temperature |
0°C to 70°C |
|
| Sensitivity |
0.05g – 0.10g / 10g / 35g / 60g / 150g |
|
| RoHS |
Compliant |
|
|
|
| |
| |
 |
|
Wireless Dry Contact Sensor
The wireless dry contact sensor can be used to detect contact between two wired contact points. This sensors can be used with an external mechanical switch or a contact plate.
- Senses immediate contact between wires.
- Senses when contact is broken.
- 36in. lead length.
« Technical Specifications
| OEM Wireless Dry Contact Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** Hardware can not withstand negative voltage. Take care when connecting a powered device.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Dry Contact Sensor Specifications |
|
|
| Supply Voltage |
2.0 - 3.6 V |
|
| Current Consumption |
0.7 µA |
|
| Operating Temperature |
[-85°C to +150°C] |
|
| |
|
|
| Absolute Maximum Ratings: |
|
|
| Supply Voltage: |
[-0.3 to 3.9 V] |
|
| Storage Temperature: |
[-50°C to +150°C]* |
|
| *Core unprogrammed |
|
|
|
|
| |
| |
 |
|
Wireless Accelerometer
The wireless accelerometer activates at given time intervals to measure the intensity and frequency of movement. Place this sensor on constantly moving objects to take periodic readings of their movement.
- Activated at set time intervals.
- Measures intensity and frequency of movement.
- User defined thresholds.
« Technical Specifications
| OEM Wireless Accelerometer - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Accelerometer Specifications |
|
|
| Supply Voltage |
2.4 – 3.6 V |
|
| Supply Current Drain (Operation mode, Pulse Detect Function Mode) |
400 µA |
|
| Supply Current Drain (Standby mode) |
2.5 µA |
|
| Operating Temperature |
-40ºC to 85ºC |
|
| Sensitivity |
58-70 count/g |
|
| Self Test Output Response |
32 - 83 count |
|
| Temperature Compensation for Offset |
±0.5 mg/°C (typ) |
|
| Temperature Sensitivity for Offset |
±0.01 mg/°C (typ) |
|
| Input High Voltage |
0.7 x Vdd |
|
| Input Low Voltage |
0.35 x Vdd |
|
| Internal Clock Frequency |
140 – 160 kHz |
|
| Bandwidth for Data Measurement |
62.5 Hz or 125 Hz |
|
| Output Data Rate |
125 Hz or 250 Hz |
|
| Nonlinearity (2 g range) |
-1 to +1 %FS |
|
| Cross Axis Sensitivity |
-5 to +5 % |
|
| RoHS |
Compliant |
|
(-40°C ≤ Ta ≤ 85°C, 2.4 V ≤ Avdd ≤ 3.6 V, Acceleration = 0g, Loaded Input) |
| |
|
| Maximum Ratings |
|
|
| Maximum Acceleration (all axes) |
5000 g |
|
| Analog Supply Voltage |
[-0.3 to +3.6 V] |
|
| Digital I/O pins Supply Voltage |
[-0.3 to +3.6 V] |
|
| Drop Test |
1.8 m |
|
| Storage Temperature Range |
[-40°C to +125°C] |
|
|
|
| |
| |
 |
|
Wireless Humidity Sensor
The wireless humidity sensor allows you to monitor the relative humidity of the air within a room or enclosure. Ideal for monitoring humidity within greenhouses, industrial spaces, museums, saunas and humidors. They can also be used for residential applications such as controlling mold, mildew or dust mites.
- Activated at set time intervals.
- Measures temperature and relative humidity.
- User defined thresholds.
« Technical Specifications
| OEM Wireless Humidity Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
** At temperatures above 100°C, programmed memory can be lost.
|
|
| Humidity Sensor Specifications |
|
|
| Accuracy: |
+/- 2% under normal conditions (50% - 90% RH) |
|
| Energy consumption: |
80uW (at 12bit, 3V, 1 measurement / s) |
|
| RH operating range: |
0 – 100% RH |
|
| T operating range: |
-40 – +125°C (-40 – +257°F) |
|
| RH response time: |
8 sec (tau63%) |
|
|
| Maximal accuracy limits for relative humdity and temperature: |
 |
|
| |
| |
 |
|
Wireless Button Sensor
The touch activated wireless button sensor allows a notification signal to be sent when immediate contact is important. This button includes an LED response indicator to confirm that the system has received the alert.
- Manually triggered push button.
- LED response indicator.
« Technical Specifications
|
| |
| |
 |
|
Wireless Motion Sensor
The wireless motion sensor uses an infrared sensor to accurately detect movements made by people/animals within 16.4 ft (5 m) range.
- Passive Infrared Technology.
- Sensing Range of 16.4 ft (5 m).
« Technical Specifications
| OEM Wireless Motion Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Infrared Motion Sensor Specifications |
|
|
| Sensing Technology |
Passive Infrared |
|
| Sensing Range |
16.4 ft (5 m) |
|
| Voltage Rating |
3 VDC to 6 VDC |
|
| Temperature Range |
–20 to +60°C (–4 to +140°F) |
|
| Output Type |
Digital |
|
| Supply Current |
170 uA |
|
|
|
| |
| |
 |
|
Wireless Lux Sensor
The wireless Lux sensor measures the intensity of light in lux (luminescence/unit area), from 0 – 1000 lux (indoor range). Perfect for light sensitive applications like museum and art gallery light monitoring.
- Highly sensitive photodiode.
- Measure luminescence from 0 – 1000 lux (indoor range).
« Technical Specifications
| OEM Wireless Lux Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Lux Sensor Specifications |
|
|
| Sensor Technology |
High Sensitive Photodiode |
|
| Material |
Silicon |
|
| Peak Wavelength |
580 nm |
|
| Maximum Reverse Voltage |
6 V |
|
| Maximum Power Dissipation |
40 mW |
|
| Maximum Light Current |
500 uA |
|
| Maximum Rise Time |
8.5 ms |
|
| Maximum Fall Time |
8.5 ms |
|
| Maximum Operating Temperature Range |
-30°C to +85°C |
|
| RoHS |
Compliant |
|
|
|
| |
| |
 |
|
Wireless 0-20 mA Sensor
The wireless 0-20 mA sensor is capable of measuring the current off another device or sensor, up to 20mA (DC), by connecting the leads on the Monnit WIT 0-20mA Current sensor to the positive and ground terminals of the device being measured. Examples of interfacing devices include, but are not limited to: Current transducers (CTs) with outputs up to 20 mA, pH sensor, dissolved oxygen sensor, pressure sensor, magnetic flow meters, velocity or acceleration sensors, industrial vibration sensors, industrial accelerometers, any kind of sensor that specifies the output is in (mA) within the range of 0 – 20.
- Interfaces with sensors or devices between 0-20 mA.
« Technical Specifications
| OEM Wireless 0-20 mA Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
|
| |
| |
 |
|
Wireless Analog Voltage Sensor
The wireless analog voltage sensor interface is capable of measuring the voltage off another device, battery, or sensor, up to 1.25 DCV by connecting the leads on the Monnit WIT Analog Voltage sensor to the positive and ground terminals of the device being measured. Examples of interfacing devices include, but are not limited to: Strain Gauge, Pressure Transducer, RTD, Thermistor, or Thermocouple, Piezo Electric sensors, Photoresistor, Industrial Accelerometer, any kind of variable resistor, any kind of sensor that outputs a voltage, etc. If the device being measured is passive, the user must supply their own excitation voltage, as the Monnit WIT Analog Voltage sensor is really just a "voltage observer". Cannot be used for AC voltage measurement.
- Interfaces with other devices up to 1.25 DCV.
« Technical Specifications
| OEM Wireless Analog Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
|
| |
| |
 |
|
Wireless Voltage Detection Sensor
The analog voltage detection sensor notifies of the presence or absence of electricity. It is intended for use on power sources or power supplies of 120 VAC. Not intended for voltages higher than 150 VAC and also not intended for use with DC sources. Perfect for sump pump monitoring. This sensor triggers on the state change from presence to absence and vice versa. The data displayed is either "No Voltage" or "Voltage Detected".
- Interfaces with other devices or power lines up to 150 VAC.
« Technical Specifications
| OEM Wireless Voltage Detection Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
|
| |
| |
 |
|
Wireless Voltage Measurement Sensor
The voltage measurement sensor is an analog measuring device that reports the measured voltage on user specified intervals. The sensor has three operating modes, in which you can obtain the voltage measurement in VACrms (root mean squared), the peak voltage, or the DC voltage. The modes can be set by the user; the default mode measures VACrms.
- Interfaces with other devices up to 500 VAC/VDC.
« Technical Specifications
| OEM Wireless Voltage Measurement Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
|
| |
| |
 |
|
Wireless Flex Sensor
The wireless flex sensor uses a flexible, stress sensitive ribbon to accurately measure the amount of bend (force) applied to the ribbon. Perfect for measurement of mechanical movement, air flow, water flow, or even vibration.
- Bend Sensor / Potentiometer.
« Technical Specifications
| OEM Wireless Flex Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Flex Sensor Specifications |
|
|
| Sensor Type |
Bend / Potentiometer |
|
| Sensor Operating Range |
-40°C to 90°C @ 90% RH typ. |
|
| Sensor Storage Temperature |
-60°C to 110°C @ 90% RH typ. |
|
| Base Resistance |
100 Ω - 500 KΩ |
|
|
|
| |
| |
 |
|
Wireless Grains Per Pound Sensor
The wireless grains per pound sensor measures the mass in grains of H2O in otherwise dry air. Put simplistically, the measurement is the weight of water in air. This sensor uses a calibrated humidity sensor to obtain the absolute humidity at the current temperature and converts that value into the Grains per Pound measurement displayed.
- Measures the weight of water in air.
- Uses a calibrated humidity sensor.
« Technical Specifications
| OEM Wireless Grains Per Pound Sensor - Technical Specifications |
|
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Humidity Sensor Specifications |
|
| Accuracy: |
+/- 2% under normal conditions (50% - 90% RH) |
|
| Energy consumption: |
80uW (at 12bit, 3V, 1 measurement / s) |
|
| RH operating range: |
0 – 100% RH |
|
| T operating range: |
-40 – +125°C (-40 – +257°F) |
|
| RH response time: |
8 sec (tau63%) |
|
|
| Maximal accuracy limits for relative humdity and temperature: |
 |
|
| |
| |
 |
|
Wireless Liquid Level Sensor
The wireless liquid level sensor uses a solid-state, resistance sensitive ribbon sensor to measure the level of a liquid in a container.
- Liquid sensitive ribbon sensor.
- Resolution of liquid level: 1/32 in.
« Technical Specifications
| OEM Wireless Liquid Level Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Liquid Level Sensor Specifications |
|
|
| Sensor Material |
Polyethylene Terephthalate (PET) |
|
| Operating Temperature Range |
-9°C to 60°C (15°F to 140°F) |
|
| Sensor Length |
10.1 inch (256.5 mm) |
|
| Active Sensor Length: |
8.6 inch (218.4 mm)) |
|
| Sensor Width |
1.0 inch (25.4 mm) |
|
| Sensor Thickness |
0.015 inch (0.381 mm) |
|
| Actuation Depth |
Nominal 1 inch (25.4 mm) |
|
| Resolution |
1/32 inch (0.794 mm) |
|
|
|
| |
| |
 |
|
Wireless Pressure Sensor
The Wireless Pressure Sensor is capable of measuring gas, liquid or vapor pressures from 0-160 PSI. This sensor can be used anywhere a pressure gauge can be used. Requires 12 – 32 VDC input. This solution combines a standard pressure transducer interfaced to an OEM Sensor wireless radio.
- Measure pressure from 0-160 PSI.
- Measure gas, liquid or vapor pressures.
- Pressure transducer is NEMA 4X, CE rated.
« Technical Specifications
| OEM Wireless Pressure Sensor - Technical Specifications |
Download Sensor Data Sheet |
| RF Board Specifications |
|
| Operating Frequency |
900 MHz (25 Channels) |
|
| Device Transmission Range |
300 - 500 ft. Non-LOS |
|
| Approximate Battery Life |
300,000 Transmissions
(~ 2-5 Years Depending on Settings*) |
|
| Supply Voltage |
2.0 - 3.6 VDC ** |
|
| Current Consumption |
0.7 μA (sleep mode)
2 mA (radio idle/off mode)
2 mA (measurement mode)
25 mA (radio RX mode)
35 mA (radio TX mode) |
|
| Operating Temperature Range |
-40°C to +85°C ( -40°F to +185°F ) *** |
|
| Optimal Battery Temperature Range (Coin Cell) |
+10°C to +60°C ( +50°F to +140°F ) |
|
| Performance |
0.7% BFSL Accuracy |
|
* Battery life depends on sensor reporting frequency and other variables.
*** At temperatures above 100°C, programmed memory can be lost.
|
|
| Pressure Sensor Specifications |
|
|
| Thermal Effect on Reading |
2% per 100 ºF |
|
| Media |
Gas, Liquid or Vapor |
|
| Dial Size |
2" (50.8 mm) |
|
| Gauge Accuracy |
1.6% full-scale Grade A (50.8 mm) |
|
| Process Connection |
¼" NPT |
|
| Proof Pressure |
0 to 160 psi = 150% of full scale |
|
| Burst Pressure |
0 to 160 psi = 10x burst |
|
| Window |
Polycarbonate or Safety Glass |
|
| Case |
304 Series Stainless Steel |
|
| Socket and Tube |
316 Series Stainless Steel |
|
| Gauge Movement |
Suppressed Stop Movement for True Electrical Zero Reading |
|
|
|
| |
| |